EPA 608 Technician Certification Safety, Cylinders, and Shipping Summary

Checked 11/1/26

Safety, Cylinders, and Shipping: key points

  • Never fill a recovery cylinder more than 80 percent full of liquid.
  • Pressurize for leak tests with nitrogen through a regulator, never oxygen or compressed air.
Importance
★★★★☆ (4 / 5)
Weight
About 5 of 25 Core questions (20%)

Health risks of refrigerant, personal protective equipment, recovery and disposable cylinders, the 80 percent fill limit, using nitrogen safely, and shipping labels.

📖 See more Safety, Cylinders, and Shipping concepts →

Safety, Cylinders, and Shipping: 10 sample questions

Practice questionReviewedCore › Safety, Cylinders, and Shipping★★★★☆

Question 1. What colors identify a refrigerant recovery cylinder?

  1. ① Solid red
  2. ② Gray body with a yellow top
  3. ③ Light blue body with a black top
  4. ④ Green body with a white top
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ② Gray body with a yellow top

Key point: Recovery cylinder: gray body, yellow top

Refillable recovery cylinders are painted with a gray body and a yellow top so they are easy to tell apart from new-refrigerant cylinders. They must be DOT-approved.

Wrong choices

  • Solid red: Solid red is not the recovery cylinder color code.
  • Light blue body with a black top: Light blue is used for some new refrigerant cylinders, not recovery cylinders.
  • Green body with a white top: Green and white is not the recovery cylinder color code.
Practice questionReviewedCore › Safety, Cylinders, and Shipping★★★★☆

Question 2. A recovery cylinder should never be filled with liquid refrigerant above what level?

  1. ① 95 percent of its capacity
  2. ② 60 percent of its capacity
  3. ③ 90 percent of its capacity
  4. ④ 80 percent of its capacity
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ④ 80 percent of its capacity

Key point: Fill recovery cylinders to 80% max

Liquid refrigerant expands when it warms. If a cylinder is too full, the liquid can fill it completely and the pressure can rise enough to burst it. Do not fill a recovery cylinder more than 80 percent full of liquid; use a scale or float switch to check.

Wrong choices

  • 95 percent of its capacity: 95 percent is dangerously full.
  • 60 percent of its capacity: 60 percent is safe but is not the usual limit.
  • 90 percent of its capacity: 90 percent leaves too little room for the liquid to expand.
Practice questionReviewedCore › Safety, Cylinders, and Shipping★★★★☆

Question 3. Which gas should be used to pressurize a system for a leak test?

  1. ① Acetylene
  2. ② Compressed air
  3. ③ Oxygen
  4. ④ Nitrogen
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ④ Nitrogen

Key point: Leak test with nitrogen, never oxygen or air

Use dry nitrogen to pressurize for leak testing. Never use oxygen or compressed air: oxygen and oil under pressure can explode, and air adds moisture.

Wrong choices

  • Acetylene: Acetylene is a flammable fuel gas.
  • Compressed air: Compressed air brings in moisture and can create an explosive mix with oil and refrigerant.
  • Oxygen: Oxygen can explode when it contacts oil under pressure.
Practice questionReviewedCore › Safety, Cylinders, and Shipping★★★★☆

Question 4. What should be done with an empty disposable (one-trip) refrigerant cylinder?

  1. ① Refill it with recovered refrigerant
  2. ② Recover any remaining refrigerant and never refill it
  3. ③ Fill it with nitrogen for leak testing
  4. ④ Use it as a recovery cylinder for small jobs
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ② Recover any remaining refrigerant and never refill it

Key point: Never refill disposable cylinders

Disposable cylinders are made for one use and must never be refilled. Any refrigerant left in them must be recovered, not vented.

Wrong choices

  • Refill it with recovered refrigerant: Disposable cylinders must never be refilled.
  • Fill it with nitrogen for leak testing: Disposable cylinders should not be reused for nitrogen or anything else.
  • Use it as a recovery cylinder for small jobs: Disposable cylinders are not recovery cylinders.
Practice questionReviewedCore › Safety, Cylinders, and Shipping★★★★☆

Question 5. Liquid refrigerant sprays on a technician's hand. What injury is most likely?

  1. ① Hearing damage
  2. ② Frostbite
  3. ③ Chemical burn from acid
  4. ④ Electrical burn
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ② Frostbite

Key point: Liquid refrigerant can cause frostbite

Liquid refrigerant boils at very low temperatures, so it can freeze skin and eyes and cause frostbite. Wear gloves and safety glasses or goggles when working with refrigerant.

Wrong choices

  • Hearing damage: A spray does not damage hearing.
  • Chemical burn from acid: Acids form only when refrigerant is heated and breaks down, not from a liquid spray.
  • Electrical burn: Refrigerant does not cause electrical burns.
Practice questionReviewedCore › Safety, Cylinders, and Shipping★★★★☆

Question 6. When pressurizing a system with nitrogen, what equipment must be used?

  1. ① Only a quick-connect fitting
  2. ② A heat gun to warm the nitrogen cylinder
  3. ③ A charging scale
  4. ④ A pressure regulator and a relief valve
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ④ A pressure regulator and a relief valve

Key point: Nitrogen: always use regulator and relief valve

A full nitrogen cylinder holds very high pressure. Always use a pressure regulator to set a safe test pressure and a relief valve to protect the system from overpressure.

Wrong choices

  • Only a quick-connect fitting: A fitting alone cannot control the high cylinder pressure.
  • A heat gun to warm the nitrogen cylinder: Heating a nitrogen cylinder is dangerous and raises pressure.
  • A charging scale: A scale does not control pressure.
Practice questionReviewedCore › Safety, Cylinders, and Shipping★★★★☆

Question 7. Why is a large refrigerant leak in a basement or closed equipment room dangerous?

  1. ① All refrigerants catch fire at room temperature
  2. ② Refrigerant vapor turns into carbon monoxide
  3. ③ Refrigerant vapor is heavier than air and can push out oxygen, causing suffocation
  4. ④ Refrigerant vapor is lighter than air and collects at the ceiling
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ③ Refrigerant vapor is heavier than air and can push out oxygen, causing suffocation

Key point: Refrigerant vapor displaces oxygen in low areas

Most refrigerant vapors are heavier than air. In a closed or low space they can displace oxygen and cause dizziness, unconsciousness, or death by suffocation. Ventilate the area, and use a self-contained breathing apparatus (SCBA) for a large leak.

Wrong choices

  • All refrigerants catch fire at room temperature: Most common refrigerants are not flammable at room temperature.
  • Refrigerant vapor turns into carbon monoxide: Refrigerant does not turn into carbon monoxide.
  • Refrigerant vapor is lighter than air and collects at the ceiling: Most refrigerant vapors are heavier than air and collect low.
Practice questionReviewedCore › Safety, Cylinders, and Shipping★★★★☆

Question 8. What labels are required on a recovery cylinder before it is shipped?

  1. ① Only the technician's certification number
  2. ② Only the date of recovery
  3. ③ No labels are needed if the cylinder is gray and yellow
  4. ④ A label naming the refrigerant and a DOT hazard classification tag
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ④ A label naming the refrigerant and a DOT hazard classification tag

Key point: Ship cylinders with refrigerant ID and DOT tag

Before shipping, a refrigerant cylinder must be labeled with the type of refrigerant and the Department of Transportation (DOT) hazard classification. Follow DOT and your reclaimer's instructions.

Wrong choices

  • Only the technician's certification number: The certification number alone does not meet shipping rules.
  • Only the date of recovery: The date alone does not meet shipping rules.
  • No labels are needed if the cylinder is gray and yellow: Cylinder colors do not replace the required labels.
Practice questionReviewedCore › Safety, Cylinders, and Shipping★★★★☆

Question 9. When is a self-contained breathing apparatus (SCBA) needed while working with refrigerant?

  1. ① During every routine gauge check
  2. ② When entering an enclosed area with a large refrigerant leak
  3. ③ Whenever recovering from a window air conditioner outdoors
  4. ④ Only when working with nitrogen
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ② When entering an enclosed area with a large refrigerant leak

Key point: SCBA for large leaks in enclosed spaces

EPA lists SCBA as protective equipment for extreme cases, such as a large leak in an enclosed area where refrigerant may have pushed out the oxygen. Gloves and goggles are the everyday protection.

Wrong choices

  • During every routine gauge check: Routine gauge checks do not require SCBA.
  • Whenever recovering from a window air conditioner outdoors: Small outdoor jobs do not normally require SCBA.
  • Only when working with nitrogen: SCBA is for oxygen-deprived air, which is mainly a concern with large refrigerant leaks.
Practice questionReviewedCore › Safety, Cylinders, and Shipping★★★★☆

Question 10. Why should a refrigerant cylinder never be heated with an open flame or torch?

  1. ① Heat raises the pressure and can make the cylinder burst
  2. ② Heat lowers the pressure and causes a vacuum
  3. ③ Heat makes the refrigerant turn into nitrogen
  4. ④ It is safe if the valve is closed
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ① Heat raises the pressure and can make the cylinder burst

Key point: Never heat a cylinder with a flame

Heating a cylinder raises the pressure inside, and a flame can weaken the metal. The cylinder can rupture violently. Never heat a cylinder with an open flame.

Wrong choices

  • Heat lowers the pressure and causes a vacuum: Heating raises pressure; it does not create a vacuum.
  • Heat makes the refrigerant turn into nitrogen: Refrigerant does not turn into nitrogen.
  • It is safe if the valve is closed: A closed valve makes it more dangerous, because pressure has nowhere to go.

Test yourself.