Clean Air Act and Section 608 Rules: key points

  • Knowingly venting CFC, HCFC, or HFC refrigerant during service or disposal is illegal.
  • Recovered refrigerant sold to a new owner must be reclaimed by an EPA-certified reclaimer.
Importance
★★★★★ (5 / 5)
Weight
About 8 of 25 Core questions (30%)

The Montreal Protocol, phaseout dates, the venting prohibition, the refrigerant sales restriction, technician certification types, reclaimed refrigerant, recordkeeping, and penalties.

📖 See more Clean Air Act and Section 608 Rules concepts →

Clean Air Act and Section 608 Rules: 10 sample questions

Practice questionReviewedCore › Clean Air Act and Section 608 Rules★★★★★

Question 1. Under the Clean Air Act, which refrigerants may NOT be knowingly vented during service, repair, or disposal of an appliance?

  1. ① Only CFCs and HCFCs
  2. ② CFCs, HCFCs, and non-exempt substitutes such as HFCs
  3. ③ Only refrigerants in systems over 50 pounds
  4. ④ Only CFCs
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ② CFCs, HCFCs, and non-exempt substitutes such as HFCs

Key point: No venting of CFC, HCFC, or non-exempt HFC

40 CFR 82.154(a) says no one servicing, repairing, or disposing of an appliance may knowingly vent CFC, HCFC, or non-exempt substitute refrigerants such as HFCs. Only a short list of substitutes (for example CO2 or nitrogen, and some hydrocarbons in certain uses) is exempt.

Wrong choices

  • Only CFCs and HCFCs: Most substitutes such as HFCs are also covered.
  • Only refrigerants in systems over 50 pounds: The venting prohibition applies to appliances of every size.
  • Only CFCs: The venting prohibition covers more than CFCs.
Practice questionReviewedCore › Clean Air Act and Section 608 Rules★★★★★

Question 2. A technician will service a split-system air conditioner that uses R-410A. Which certification is required?

  1. ① Type II or Universal
  2. ② Section 609 (motor vehicle) certification
  3. ③ Type III
  4. ④ Type I
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ① Type II or Universal

Key point: High-pressure (R-410A, R-22) systems = Type II

R-410A is a high-pressure refrigerant. Servicing or disposing of medium-, high-, or very high-pressure appliances (other than small appliances and motor vehicle systems) requires Type II certification, which is also included in Universal.

Wrong choices

  • Section 609 (motor vehicle) certification: Section 609 is for motor vehicle air conditioning.
  • Type III: Type III covers low-pressure appliances such as R-123 chillers.
  • Type I: Type I covers only small factory-sealed appliances with 5 pounds or less.
Practice questionReviewedCore › Clean Air Act and Section 608 Rules★★★★★

Question 3. Recovered refrigerant is going to be sold to a different owner. What must be done first?

  1. ① It must be mixed with new refrigerant
  2. ② It only needs to pass through a recycling machine
  3. ③ It must be reclaimed by an EPA-certified reclaimer
  4. ④ Nothing; recovered refrigerant may be sold as is
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ③ It must be reclaimed by an EPA-certified reclaimer

Key point: Change of owner = must be reclaimed

Under 40 CFR 82.154(d), used refrigerant may not be sold to a new owner unless it has been reclaimed by a certified reclaimer to the purity standard in Appendix A (based on AHRI Standard 700).

Wrong choices

  • It must be mixed with new refrigerant: Mixing does not make used refrigerant legal to sell.
  • It only needs to pass through a recycling machine: Recycling cleans refrigerant for the same owner, but it does not meet the standard for sale to a new owner.
  • Nothing; recovered refrigerant may be sold as is: Used refrigerant cannot be sold to a new owner without reclamation.
Practice questionReviewedCore › Clean Air Act and Section 608 Rules★★★★★

Question 4. What is the Montreal Protocol?

  1. ① A U.S. law that sets electrical codes for HVAC equipment
  2. ② An EPA rule for car air conditioning only
  3. ③ An international treaty to phase out production of ozone-depleting substances
  4. ④ A safety standard for refrigerant cylinders
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ③ An international treaty to phase out production of ozone-depleting substances

Key point: Montreal Protocol: global ODS phaseout treaty

The Montreal Protocol is the international agreement to phase out the production of ozone-depleting substances such as CFCs and HCFCs. The United States carries it out through the Clean Air Act.

Wrong choices

  • A U.S. law that sets electrical codes for HVAC equipment: The Montreal Protocol is not about electrical codes.
  • An EPA rule for car air conditioning only: It is worldwide and covers all uses of ozone-depleting substances, not just cars.
  • A safety standard for refrigerant cylinders: Cylinder safety is covered by DOT rules, not the Montreal Protocol.
Practice questionReviewedCore › Clean Air Act and Section 608 Rules★★★★★

Question 5. Which of these gases may be released to the air without breaking the venting prohibition?

  1. ① R-410A
  2. ② Pure nitrogen used for a leak test
  3. ③ R-134a
  4. ④ R-22
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ② Pure nitrogen used for a leak test

Key point: Nitrogen and CO2 are exempt from venting ban

EPA lists a few substitutes as exempt from the venting prohibition, including nitrogen, carbon dioxide, and water in any application. CFCs, HCFCs, and HFCs such as R-410A and R-134a may not be vented.

Wrong choices

  • R-410A: R-410A is an HFC blend covered by the venting prohibition.
  • R-134a: R-134a is an HFC and may not be vented.
  • R-22: R-22 is an HCFC and may not be vented.
Practice questionReviewedCore › Clean Air Act and Section 608 Rules★★★★★

Question 6. Under the refrigerant sales restriction, who may buy a 25-pound cylinder of R-410A for servicing stationary equipment?

  1. ① Any licensed electrician
  2. ② Any adult with a photo ID
  3. ③ A Section 608 certified technician, or a business that employs one
  4. ④ Any building owner, for use in their own building
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ③ A Section 608 certified technician, or a business that employs one

Key point: Only certified techs may buy non-exempt refrigerant

40 CFR 82.154(c) limits sales of CFC, HCFC, and non-exempt substitute refrigerants such as HFCs to certified technicians (Type I, II, III, or Universal), or to buyers who employ a certified technician and show proof. There are a few exceptions, such as sales for resale.

Wrong choices

  • Any licensed electrician: An electrical license does not meet the Section 608 sales restriction.
  • Any adult with a photo ID: A photo ID alone is not enough; the buyer must be certified or employ a certified technician.
  • Any building owner, for use in their own building: Owning a building does not allow buying refrigerant without certification.
Practice questionReviewedCore › Clean Air Act and Section 608 Rules★★★★★

Question 7. How long is EPA Section 608 technician certification valid?

  1. ① 3 years
  2. ② 1 year
  3. ③ It does not expire
  4. ④ 5 years
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ③ It does not expire

Key point: Section 608 certification does not expire

EPA states that Section 608 technician certification does not expire. EPA keeps the right to require recertification in the future by a notice in the Federal Register. Technicians must keep a copy of their certificate at their place of business.

Wrong choices

  • 3 years: Three years is a recordkeeping period, not a certification term.
  • 1 year: There is no yearly renewal.
  • 5 years: There is no 5-year renewal for Section 608 certification.
Practice questionReviewedCore › Clean Air Act and Section 608 Rules★★★★★

Question 8. In the United States, production and import of CFC refrigerants such as R-12 ended on which date?

  1. ① January 1, 2020
  2. ② January 1, 1996
  3. ③ January 1, 2010
  4. ④ January 1, 1990
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ② January 1, 1996

Key point: CFC production and import ban: January 1, 1996

EPA's ban on production and import of most class I ozone-depleting substances, including CFCs, took effect on January 1, 1996. Existing CFC refrigerant can still be recovered, recycled, and reclaimed for use.

Wrong choices

  • January 1, 2020: 2020 is when production and import of HCFC-22 (R-22) ended.
  • January 1, 2010: 2010 is when production of HCFC-22 for new equipment ended.
  • January 1, 1990: CFC production was still allowed in 1990.
Practice questionReviewedCore › Clean Air Act and Section 608 Rules★★★★★

Question 9. When did production and import of HCFC-22 (R-22) end in the United States?

  1. ① January 1, 2015
  2. ② January 1, 2020
  3. ③ January 1, 2030
  4. ④ January 1, 1996
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ② January 1, 2020

Key point: R-22 production and import ended January 1, 2020

Under the HCFC phaseout, production and import of HCFC-22 ended in 2020. Existing systems can still be serviced with R-22 that was produced before then or that is recovered, recycled, or reclaimed.

Wrong choices

  • January 1, 2015: In 2015 limits tightened on other HCFCs, but R-22 production had not yet ended.
  • January 1, 2030: 2030 is when production and import of all remaining HCFCs ends.
  • January 1, 1996: 1996 is the CFC production ban.
Practice questionReviewedCore › Clean Air Act and Section 608 Rules★★★★★

Question 10. Which release of refrigerant is allowed as a "de minimis" release?

  1. ① A small release while connecting or disconnecting hoses during proper recovery
  2. ② Venting the last few pounds to save time at disposal
  3. ③ Releasing refrigerant from a cylinder to lower its pressure
  4. ④ Purging a whole charge to clear air from the system
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ① A small release while connecting or disconnecting hoses during proper recovery

Key point: De minimis = tiny release during good-faith recovery

De minimis releases are small amounts released during a good-faith attempt to recover refrigerant while following the required practices, such as when connecting or disconnecting hoses. Knowingly venting any other refrigerant is a violation.

Wrong choices

  • Venting the last few pounds to save time at disposal: Venting to save time is a knowing release and is illegal.
  • Releasing refrigerant from a cylinder to lower its pressure: Venting from a cylinder is a knowing release after recovery, which is a violation.
  • Purging a whole charge to clear air from the system: Purging a whole charge is illegal venting.