EPA 608 Technician Certification Low-Pressure Chillers, Purge Units, and Safety Summary
Checked 11/1/26
Low-Pressure Chillers, Purge Units, and Safety: key points
- The purge unit removes air and moisture that collect at the top of the condenser.
- R-123 machinery rooms need a refrigerant sensor under ASHRAE Standard 15.
- Importance
- ★★★☆☆ (3 / 5)
- Weight
- About 6 of 25 Type III (Low-Pressure) questions (25%)
How low-pressure chillers work, the purge unit, the rupture disc, low-pressure refrigerants such as R-123 and R-11, and machinery room safety.
📖 See more Low-Pressure Chillers, Purge Units, and Safety concepts →Low-Pressure Chillers, Purge Units, and Safety: 9 sample questions
Question 1. What does the purge unit on a low-pressure chiller do?
- ① Adds refrigerant automatically
- ② Cools the compressor oil
- ③ Relieves pressure if the chiller gets too hot
- ④ Removes air and moisture (noncondensables) from the system
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ④ Removes air and moisture (noncondensables) from the system
Key point: Purge unit removes air and moisture
Air and moisture leak into low-pressure chillers. The purge unit removes these noncondensables while returning as much refrigerant as possible to the system. High-efficiency purge units release very little refrigerant.
Wrong choices
- Adds refrigerant automatically: The purge unit does not charge refrigerant.
- Cools the compressor oil: It does not cool the oil.
- Relieves pressure if the chiller gets too hot: Pressure relief is the job of the rupture disc or relief valve.
Question 2. R-123 replaced which older CFC refrigerant in many low-pressure chillers?
- ① R-12
- ② R-502
- ③ R-22
- ④ R-11
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ④ R-11
Key point: R-123 (HCFC) replaced R-11 (CFC)
R-123, an HCFC, became the common replacement for R-11, a CFC, in low-pressure centrifugal chillers. Both are low-pressure refrigerants.
Wrong choices
- R-12: R-12 is a medium-pressure CFC used in other equipment.
- R-502: R-502 is a high-pressure blend.
- R-22: R-22 is a high-pressure HCFC.
Question 3. While a low-pressure chiller is running, what is the pressure in its evaporator?
- ① Below atmospheric pressure (a vacuum)
- ② About 300 psig
- ③ Exactly 0 psig at all times
- ④ About 100 psig
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ① Below atmospheric pressure (a vacuum)
Key point: Low-pressure evaporator runs in a vacuum
Low-pressure refrigerants such as R-123 boil at low temperatures only under vacuum, so the evaporator runs below atmospheric pressure. This is why leaks let air in.
Wrong choices
- About 300 psig: 300 psig is typical of high-pressure systems, not low-pressure chillers.
- Exactly 0 psig at all times: The pressure is normally below 0 psig while running.
- About 100 psig: 100 psig is far too high for a low-pressure evaporator.
Question 4. From where in a low-pressure chiller does the purge unit take its sample?
- ① The top of the condenser, where noncondensables collect
- ② The oil sump
- ③ The water box
- ④ The bottom of the evaporator
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ① The top of the condenser, where noncondensables collect
Key point: Purge pulls from top of condenser
Air and other noncondensables are trapped at the top of the condenser because they do not condense. The purge unit draws from there to remove them.
Wrong choices
- The oil sump: The oil sump is not where noncondensables collect.
- The water box: The water box holds water, not refrigerant.
- The bottom of the evaporator: The bottom of the evaporator holds liquid refrigerant, not trapped air.
Question 5. At what pressure is the rupture disc on a low-pressure chiller's evaporator usually set to burst?
- ① 15 psig
- ② 10 psig
- ③ 50 psig
- ④ 150 psig
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ① 15 psig
Key point: Rupture disc on low-pressure chiller: 15 psig
The rupture disc protects the low-pressure chiller from overpressure and is usually set at 15 psig. That is why leak test pressure is kept at 10 psig or less.
Wrong choices
- 10 psig: 10 psig is the usual maximum leak test pressure, kept below the disc setting.
- 50 psig: 50 psig is far above the usual setting.
- 150 psig: 150 psig is a high-pressure range.
Question 6. Under ASHRAE Standard 15, what is required in a machinery room with an R-123 chiller?
- ① Only a first aid kit
- ② Only a fire extinguisher
- ③ A window that stays open
- ④ A refrigerant sensor (detector) that sounds an alarm
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ④ A refrigerant sensor (detector) that sounds an alarm
Key point: R-123 machinery room needs refrigerant sensor
EPA's Type III test topics state that ASHRAE Standard 15 requires an equipment room refrigerant sensor for R-123, along with the oxygen-deprivation protection that applies to all refrigerants.
Wrong choices
- Only a first aid kit: A first aid kit alone does not meet this rule.
- Only a fire extinguisher: A fire extinguisher alone does not meet this rule.
- A window that stays open: An open window does not replace a refrigerant sensor.
Question 7. A large R-123 leak happens in a closed machinery room. What is the main danger to a technician who enters?
- ① Lack of oxygen, because refrigerant vapor pushes out the air
- ② Electric shock from the refrigerant
- ③ Radiation exposure
- ④ Hearing damage from the leak noise
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ① Lack of oxygen, because refrigerant vapor pushes out the air
Key point: Big leak in a room = oxygen deprivation
Refrigerant vapor is heavier than air and can displace oxygen. Do not enter without checking the alarm and using a self-contained breathing apparatus (SCBA) if needed. Ventilate the room.
Wrong choices
- Electric shock from the refrigerant: Refrigerant does not cause electric shock.
- Radiation exposure: Refrigerant is not radioactive.
- Hearing damage from the leak noise: Noise is not the main danger.
Question 8. A low-pressure chiller holding R-123 is shut down in a 75°F room. What pressure is it most likely to show?
- ① About 200 psig
- ② About 100 psig
- ③ Slightly below atmospheric (a small vacuum)
- ④ Exactly 15 psig
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ③ Slightly below atmospheric (a small vacuum)
Key point: R-123 at room temp: near 0 psig, slight vacuum
R-123 boils at about 82°F at atmospheric pressure. At 75°F, its saturation pressure is a little below atmospheric, so a shut-down chiller shows a slight vacuum. Use the pressure-temperature relationship of low-pressure refrigerants to judge readings.
Wrong choices
- About 200 psig: 200 psig is a high-pressure range.
- About 100 psig: 100 psig is far too high for R-123 at room temperature.
- Exactly 15 psig: 15 psig would be near the rupture disc setting.
Question 9. All of the following are low-pressure refrigerants EXCEPT:
- ① R-113
- ② R-134a
- ③ R-11
- ④ R-123
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ② R-134a
Key point: R-134a is medium-pressure
R-134a is listed as a medium-pressure refrigerant (covered by Type II). R-11, R-123, and R-113 are low-pressure refrigerants (Type III).
Wrong choices
- R-113: R-113 is a low-pressure refrigerant.
- R-11: R-11 is a low-pressure refrigerant.
- R-123: R-123 is a low-pressure refrigerant.
Test yourself.