EPA 608 Technician Certification Low-Pressure Recovery, Evacuation, and Recharging Summary

Checked 11/1/26

Low-Pressure Recovery, Evacuation, and Recharging: key points

  • Low-pressure appliances must be evacuated to 25 mm Hg absolute.
  • When recharging, add vapor first so water in the tubes does not freeze.
Importance
★★★★★ (5 / 5)
Weight
About 10 of 25 Type III (Low-Pressure) questions (40%)

The 25 mm Hg absolute evacuation level, recovering liquid and then vapor, keeping water moving in the tubes, heating oil before draining, pressurizing for non-major repairs, and charging vapor before liquid.

📖 See more Low-Pressure Recovery, Evacuation, and Recharging concepts →

Low-Pressure Recovery, Evacuation, and Recharging: 10 sample questions

Practice questionReviewedType III (Low-Pressure) › Low-Pressure Recovery, Evacuation, and Recharging★★★★★

Question 1. To what level must a low-pressure appliance be evacuated before it is opened for a major repair or disposal?

  1. ① 10 inches of mercury vacuum
  2. ② 0 psig
  3. ③ 25 mm Hg absolute
  4. ④ 4 inches of mercury vacuum
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ③ 25 mm Hg absolute

Key point: Low-pressure appliances: 25 mm Hg absolute

Table 1 in 40 CFR 82.156 requires low-pressure appliances to be evacuated to 25 mm Hg absolute, which is a deep vacuum of about 29 inches of mercury.

Wrong choices

  • 10 inches of mercury vacuum: 10 inches applies to some large high- and medium-pressure appliances.
  • 0 psig: 0 psig is for non-major repairs.
  • 4 inches of mercury vacuum: 4 inches applies to small appliances and older equipment on some appliances.
Practice questionReviewedType III (Low-Pressure) › Low-Pressure Recovery, Evacuation, and Recharging★★★★★

Question 2. During refrigerant recovery from a chiller, why should water be circulated through the tubes or drained?

  1. ① To add moisture to the refrigerant
  2. ② To keep the purge unit running
  3. ③ To keep the water in the tubes from freezing
  4. ④ To speed up the compressor
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ③ To keep the water in the tubes from freezing

Key point: Keep water moving to prevent tube freezing

As pressure drops during recovery, the refrigerant gets very cold. If water sits still in the tubes it can freeze and burst them, so water should be circulated or drained during evacuation.

Wrong choices

  • To add moisture to the refrigerant: Moisture in refrigerant is unwanted.
  • To keep the purge unit running: It is not done to run the purge unit.
  • To speed up the compressor: This step protects the tubes; it is not for the compressor.
Practice questionReviewedType III (Low-Pressure) › Low-Pressure Recovery, Evacuation, and Recharging★★★★★

Question 3. When recovering refrigerant from a low-pressure chiller, what should be removed first?

  1. ① The liquid refrigerant
  2. ② The water in the tubes
  3. ③ The vapor
  4. ④ The oil
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ① The liquid refrigerant

Key point: Low-pressure recovery: liquid first, then vapor

Recovering liquid first speeds up the job because most of the refrigerant is liquid. After the liquid is out, the remaining vapor must also be recovered.

Wrong choices

  • The water in the tubes: Water in the tubes should keep moving or be drained to prevent freezing; it is not recovered first.
  • The vapor: Vapor is recovered after the liquid.
  • The oil: Oil is not recovered first.
Practice questionReviewedType III (Low-Pressure) › Low-Pressure Recovery, Evacuation, and Recharging★★★★★

Question 4. When recharging a low-pressure chiller after it has been evacuated, what should be added first?

  1. ① Liquid refrigerant
  2. ② Refrigerant vapor
  3. ③ Nitrogen
  4. ④ Oil
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ② Refrigerant vapor

Key point: Recharge with vapor first, then liquid

Under a deep vacuum, liquid refrigerant would boil and become very cold, which can freeze water in the tubes. Charge vapor first until the pressure is high enough (above the saturation pressure for 32°F), and then add liquid.

Wrong choices

  • Liquid refrigerant: Adding liquid first under a deep vacuum can make it boil and freeze the water in the tubes.
  • Nitrogen: Nitrogen is not used to start charging.
  • Oil: Oil is not added first in place of refrigerant.
Practice questionReviewedType III (Low-Pressure) › Low-Pressure Recovery, Evacuation, and Recharging★★★★★

Question 5. After the liquid is removed from a large low-pressure chiller, why must the vapor also be recovered?

  1. ① Vapor contains only air
  2. ② A large amount of refrigerant remains as vapor in the big shell
  3. ③ Vapor can be vented legally from low-pressure systems
  4. ④ The rupture disc needs vapor to stay closed
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ② A large amount of refrigerant remains as vapor in the big shell

Key point: Big chillers hold many pounds as vapor

A large chiller has a big volume, so a significant amount of refrigerant stays as vapor after the liquid is removed. EPA's test topics stress the need to recover vapor in addition to liquid.

Wrong choices

  • Vapor contains only air: The vapor is mostly refrigerant, not just air.
  • Vapor can be vented legally from low-pressure systems: Venting refrigerant vapor is illegal.
  • The rupture disc needs vapor to stay closed: This is not why vapor is recovered.
Practice questionReviewedType III (Low-Pressure) › Low-Pressure Recovery, Evacuation, and Recharging★★★★★

Question 6. Before draining oil from a low-pressure chiller, to what temperature should the oil be heated?

  1. ① 212°F
  2. ② 130°F
  3. ③ 32°F
  4. ④ 70°F
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ② 130°F

Key point: Heat oil to 130°F before draining

Refrigerant dissolves in oil. EPA's test topics say to heat the oil to 130°F before removing it, which drives out more refrigerant so less is lost with the oil.

Wrong choices

  • 212°F: 212°F is too hot and is not the guideline.
  • 32°F: Cold oil holds more refrigerant.
  • 70°F: 70°F leaves more refrigerant dissolved in the oil.
Practice questionReviewedType III (Low-Pressure) › Low-Pressure Recovery, Evacuation, and Recharging★★★★☆

Question 7. Through which valve should a centrifugal chiller usually be charged?

  1. ① The condenser water drain
  2. ② The rupture disc
  3. ③ The purge unit vent
  4. ④ The evaporator charging valve
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ④ The evaporator charging valve

Key point: Charge centrifugals through evaporator charging valve

EPA's test topics say centrifugal chillers are charged through the evaporator charging valve, starting with vapor until the pressure is high enough to add liquid safely.

Wrong choices

  • The condenser water drain: The water drain is not part of the refrigerant circuit.
  • The rupture disc: The rupture disc is a safety device, not a valve.
  • The purge unit vent: The purge vent is not a charging connection.
Practice questionReviewedType III (Low-Pressure) › Low-Pressure Recovery, Evacuation, and Recharging★★★★☆

Question 8. After reaching 25 mm Hg absolute, a technician waits and the chiller pressure rises. What should the technician do?

  1. ① Open the chiller right away
  2. ② Stop, because the pressure rise means the job is done
  3. ③ Continue recovery, because refrigerant is still boiling off from liquid or oil
  4. ④ Add nitrogen and vent it
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ③ Continue recovery, because refrigerant is still boiling off from liquid or oil

Key point: Pressure rise after recovery: keep recovering

EPA's test topics say to wait a few minutes after reaching the required vacuum. If pressure rises, liquid refrigerant or refrigerant in the oil remains, so recovery should continue.

Wrong choices

  • Open the chiller right away: Opening now would release refrigerant.
  • Stop, because the pressure rise means the job is done: A pressure rise means refrigerant is still there.
  • Add nitrogen and vent it: Venting is illegal.
Practice questionReviewedType III (Low-Pressure) › Low-Pressure Recovery, Evacuation, and Recharging★★★★☆

Question 9. Does the required evacuation level for a low-pressure appliance change if the recovery equipment was made before November 15, 1993?

  1. ① Yes; older equipment needs only 0 psig
  2. ② Yes; older equipment needs only 4 inches of mercury vacuum
  3. ③ No; it is 25 mm Hg absolute for both older and newer equipment
  4. ④ Yes; older equipment needs 15 inches of mercury vacuum
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ③ No; it is 25 mm Hg absolute for both older and newer equipment

Key point: 25 mm Hg absolute: same for old and new equipment

In Table 1, the level for low-pressure appliances is 25 mm Hg absolute in both columns: equipment made before and on or after November 15, 1993.

Wrong choices

  • Yes; older equipment needs only 0 psig: 0 psig is for non-major repairs.
  • Yes; older equipment needs only 4 inches of mercury vacuum: 4 inches applies to some medium- and high-pressure appliances with older equipment, not low-pressure ones.
  • Yes; older equipment needs 15 inches of mercury vacuum: 15 inches is for large medium-pressure appliances with newer equipment.
Practice questionReviewedType III (Low-Pressure) › Low-Pressure Recovery, Evacuation, and Recharging★★★★☆

Question 10. For a non-major repair on a low-pressure chiller using a refrigerant that boils above 85°F at atmospheric pressure (such as R-113), how may the pressure be raised to atmospheric (0 psig) before opening?

  1. ① Leave it in a vacuum and open it
  2. ② Use compressed air
  3. ③ Use heat first, then nitrogen if needed to reach atmospheric pressure
  4. ④ Use nitrogen only, with no heat
▼ Show answer and explanation▲ Hide answer and explanation

Answer: ③ Use heat first, then nitrogen if needed to reach atmospheric pressure

Key point: Low-pressure non-major repair: raise to 0 psig

Under 40 CFR 82.156(a)(1)(ii), low-pressure appliances are pressurized to 0 psig before opening for a non-major repair. For refrigerants that boil above 85°F (such as R-113), use heat first and then nitrogen if needed. For refrigerants that boil at or below 85°F (such as R-11 and R-123), methods such as nitrogen that need later purging may not be used.

Wrong choices

  • Leave it in a vacuum and open it: Opening under vacuum draws in air and moisture; the rule requires 0 psig.
  • Use compressed air: Compressed air is not an allowed method.
  • Use nitrogen only, with no heat: The rule says heat must be used first to raise pressure as much as possible.

Test yourself.