EPA 608 Technician Certification High-Pressure Leak Detection and Leak Repair Summary
Checked 11/1/26
High-Pressure Leak Detection and Leak Repair: key points
- Trigger leak rates: 20% commercial, 30% industrial process, 10% comfort cooling and others.
- Repair within 30 days (120 days if an industrial process shutdown is needed).
- Importance
- ★★★★★ (5 / 5)
- Weight
- About 9 of 25 Type II (High-Pressure) questions (35%)
Signs of leaks, leak test gases, leak rate triggers for large appliances, repair deadlines, verification tests, leak inspections, retrofit or retirement plans, and leak repair records.
📖 See more High-Pressure Leak Detection and Leak Repair concepts →High-Pressure Leak Detection and Leak Repair: 10 sample questions
Question 1. A comfort cooling system holds 80 pounds of R-22. Above what annual leak rate must the owner repair the leaks?
- ① 30 percent
- ② 20 percent
- ③ 35 percent
- ④ 10 percent
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ④ 10 percent
Key point: Comfort cooling (50 lb+ ODS): 10% trigger
Under 40 CFR 82.157(c), appliances with 50 or more pounds of ozone-depleting refrigerant must be repaired when the leak rate is over 10 percent for comfort cooling (and other appliances), 20 percent for commercial refrigeration, and 30 percent for industrial process refrigeration.
Wrong choices
- 30 percent: 30 percent is the trigger for industrial process refrigeration.
- 20 percent: 20 percent is the trigger for commercial refrigeration.
- 35 percent: 35 percent was an older trigger rate that no longer applies.
Question 2. A supermarket refrigeration system holds 200 pounds of R-22. Above what annual leak rate must it be repaired?
- ① 30 percent
- ② 20 percent
- ③ 15 percent
- ④ 10 percent
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ② 20 percent
Key point: Commercial refrigeration: 20% trigger
Supermarket and cold-storage systems are commercial refrigeration. With 50 or more pounds of ozone-depleting refrigerant, leaks must be repaired when the leak rate exceeds 20 percent per year.
Wrong choices
- 30 percent: 30 percent is the trigger for industrial process refrigeration.
- 15 percent: 15 percent was an older comfort cooling trigger.
- 10 percent: 10 percent is the trigger for comfort cooling and other appliances.
Question 3. Once an appliance is found leaking above its trigger rate, how long does the owner normally have to repair the leaks?
- ① 90 days
- ② 10 days
- ③ 30 days
- ④ 1 year
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ③ 30 days
Key point: Leak repair deadline: 30 days
Under 40 CFR 82.157(d), leaks must be repaired within 30 days of adding refrigerant to an appliance that exceeds the trigger rate, or 120 days if an industrial process shutdown is needed.
Wrong choices
- 90 days: 90 days is not the standard repair period.
- 10 days: 10 days is the time limit for the follow-up verification test, not the repair.
- 1 year: One year is the time to complete a retrofit or retirement plan.
Question 4. Which is a common sign of a refrigerant leak in a high-pressure system?
- ① Traces of oil around joints or fittings
- ② A clean, dry condenser coil
- ③ Low noise from the compressor
- ④ Frost on the outside of the recovery cylinder
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ① Traces of oil around joints or fittings
Key point: Oil traces at joints = possible leak
Refrigerant carries oil, so oil traces around joints, fittings, and hermetic compressor connections are a common sign of a leak. Excessive superheat is another sign.
Wrong choices
- A clean, dry condenser coil: A clean, dry coil is not a sign of a leak.
- Low noise from the compressor: Compressor noise level is not a typical leak sign.
- Frost on the outside of the recovery cylinder: Frost on a recovery cylinder is normal during recovery and is not a leak sign on the system.
Question 5. When should a system be leak tested?
- ① Never; the compressor will show any leaks
- ② Only once a year in the spring
- ③ Before charging or recharging it with refrigerant
- ④ Only after the system has been fully charged
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ③ Before charging or recharging it with refrigerant
Key point: Leak test before charging
EPA's test topics stress the need to leak test before charging or recharging equipment, so refrigerant is not lost through a leak that could have been found first.
Wrong choices
- Never; the compressor will show any leaks: A compressor does not reveal leaks.
- Only once a year in the spring: Leak testing is needed before charging, whatever the season.
- Only after the system has been fully charged: Testing after charging wastes refrigerant if there is a leak.
Question 6. An industrial process refrigeration system holds 600 pounds of an HCFC. Above what annual leak rate must it be repaired?
- ① 10 percent
- ② 20 percent
- ③ 30 percent
- ④ 35 percent
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ③ 30 percent
Key point: Industrial process refrigeration: 30% trigger
For industrial process refrigeration (chemical plants, industrial ice machines, ice rinks, and similar), the leak repair trigger is 30 percent per year for appliances with 50 or more pounds of ozone-depleting refrigerant.
Wrong choices
- 10 percent: 10 percent is the trigger for comfort cooling.
- 20 percent: 20 percent is the trigger for commercial refrigeration.
- 35 percent: 35 percent was the older trigger before the 2016 rule.
Question 7. An owner decides to retire a leaking appliance instead of repairing it. What must be done?
- ① Create a retirement plan within 30 days and finish it within 1 year
- ② Retire it within 10 days with no plan
- ③ Nothing, as long as refrigerant is added each month
- ④ Send a letter to EPA within 1 year
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ① Create a retirement plan within 30 days and finish it within 1 year
Key point: Retrofit/retire plan: 30 days, done within 1 year
Under 40 CFR 82.157(h), an owner who chooses to retrofit or retire must create a written plan within 30 days and complete the work within one year of the plan's date, unless granted more time.
Wrong choices
- Retire it within 10 days with no plan: The rule requires a written plan, and 10 days is not the deadline.
- Nothing, as long as refrigerant is added each month: Topping off a leaking appliance does not meet the rule.
- Send a letter to EPA within 1 year: A letter to EPA is not the requirement.
Question 8. For an appliance subject to leak repair rules, when must the owner calculate the leak rate?
- ① Only when it is disposed of
- ② Only when the appliance stops cooling
- ③ Once every 5 years
- ④ Each time refrigerant is added (with a few exceptions)
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ④ Each time refrigerant is added (with a few exceptions)
Key point: Calculate leak rate every time refrigerant is added
Under 40 CFR 82.157(b), the owner must calculate the leak rate every time refrigerant is added, except right after a retrofit, a new installation, or a seasonal variance. The technician must give the owner a record of the amount added.
Wrong choices
- Only when it is disposed of: Disposal is not when leak rates are calculated.
- Only when the appliance stops cooling: Waiting until the appliance fails is too late.
- Once every 5 years: The rule requires a calculation each time refrigerant is added.
Question 9. In a high-pressure system, what operating sign may point to a refrigerant leak?
- ① Ice-cold liquid line
- ② Very low superheat
- ③ Excessive superheat
- ④ High suction pressure
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ③ Excessive superheat
Key point: Low charge from a leak → excessive superheat
When refrigerant leaks out, less refrigerant reaches the evaporator. It boils off early and the vapor picks up extra heat, so superheat becomes excessive. EPA lists this as a sign of leakage in high-pressure systems.
Wrong choices
- Ice-cold liquid line: This is not a typical sign of a leak.
- Very low superheat: Very low superheat often means overcharge or too much refrigerant flow, not a leak.
- High suction pressure: A leak usually lowers suction pressure.
Question 10. Under 40 CFR 82.157, the leak repair rules apply to appliances containing how much ozone-depleting (CFC or HCFC) refrigerant?
- ① 5 pounds or more
- ② 15 pounds or more
- ③ 50 pounds or more
- ④ 200 pounds or more
▼ Show answer and explanation▲ Hide answer and explanation
Answer: ③ 50 pounds or more
Key point: Part 82 leak repair: 50 lb+ of ODS refrigerant
40 CFR 82.157 applies to appliances with a full charge of 50 or more pounds of a CFC or HCFC refrigerant (or a blend containing one). Appliances with only substitute refrigerants are not covered by this section; HFC appliances now fall under Part 84.
Wrong choices
- 5 pounds or more: 5 pounds is the small appliance limit.
- 15 pounds or more: 15 pounds is the threshold in the newer Part 84 rule for HFCs, not Part 82.
- 200 pounds or more: 200 pounds is a break point in the evacuation table, not leak repair.